TitleProduct

Air to Water Heat Pump 25kw

  • Price:

    Negotiable

  • minimum:

  • Total supply:

  • Delivery term:

    The date of payment from buyers deliver within days

  • seat:

    Zhejiang

  • Validity to:

    Long-term effective

  • Last update:

    2017-11-13 20:12

  • Browse the number:

    43

Send an inquiries

Company Profile

GUANG ZHOU FENLIN SANGNA SHEBEI CO., LTD.

By certification [File Integrity]

Contact:Mr. Alan Lin(Mr.)  

Email:

Telephone:

Phone:

Area:Zhejiang

Address:Zhejiang

Website: http://mesheatpump.auto-charge.net/

PRODUCT DETAILS
MES Commercial air source heat pump for 50ºC hot water 
 
This is air source circulation type heat pump for commercial hot water rated temperature 50ºC,
Adjustment range from 28ºC to 60ºC, we have the unique design with world famous brand of components, with the testing by our engineer with 15 years experiences, we can ensure the best performance for you.
 
 Product Info.
Compressor Copeland scroll or Panasonic scroll
Capacity 12KW, 19KW,25KW, 35KW, 50KW, 65KW, 75KW, 85KW, 105KW, 125KW, 165KW
Refrigerant R410A
Condenser "ND" Shell & Coil heat exchanger
Evaporator Finned tube heat exchanger(High quality, stainless steel 304 for frame)
Fan motor Axial
Fan blades Metal
AC contactor & Relay Schneider
Electronic expansion valve Japan Saginomiya or World No.1 Sanhua
Reversing valve World No.1 Sanhua
Controller LCD
Package Wooden case or Carton
Fasteners Stainless steel 304
 
 Additional Info.
Delivery time 25 days after order confirmed
Warranty time 24 months after shipment
Payment term T/T or L/C at sight
Production capacity 400 units per month
Brand MES or OEM

 WHY US?


Components brands we use:


BEST DESIGN FOR BEST OPERATION!
PRODUCT FEATURES:


a. Copeland and R410a refrigerant for best operation.
b. Stainless steel 304 material for all fasterners, frame of evaporator and etc..
c. Low noise fan motor with metal fan blades, Durable and reliable.
d. World famous brands of components, such as Saginomiya electronic expansion valves, SHF 4-way valves and etc.,
e. With compelete testing in laboratory for good quality and highest COP.
f. All copper material for water pipes.
g. Strong wooden case packing for safe sea transporation.
h. Advanced control system for reaching all of your requirements, such as Rs485, PC connection, Modbus port.
i. Unique cabinet designing, for your better marketing.


Parameters table:
  BG12s-N3 BG19s-N5 BG12-N3 BG19-N5 BG25-N5 BG35-N10 BG50-N10 BG65-N10 BG75-N20 BG85-N20 BG105-N20 BG125-N20 BG165-N40
Rated heating capacity kW 12 19 12 19 25 35 50 65 75 85 105 125 165
Rated input power kW 2.72 4.29 2.71 4.28 5.64 7.92 11.36 14.73 16.89 19.19 23.70 28.28 37.33
Rated input current A 11.88 18.73 4.94 7.79 10.27 14.41 20.68 27.83 30.74 34.92 43.14 51.47 67.94
Maximum input power kW 3.54 5.58 3.53 5.56 7.34 10.29 14.77 18.85 21.96 24.94 30.81 36.76 48.53
Maximum input current A 15.45 24.35 6.67 10.51 13.87 19.46 27.92 35.80 41.50 47.14 58.24 69.49 91.72
Performance coefficient(COP) / 4.41 4.43 4.42 4.44 4.43 4.42 4.40 4.41 4.44 4.43 4.43 4.42 4.42
Setting water temperature ºC 50ºC(default) 28-60ºC(adjustable)
Rated hot water yields L/H 258 408 258 408 537 752.5 1075 1397.5 1612.5 1827.5 2257.5 2687.5 3547.5
Power supply 1N 220V/50Hz
(Special power supply for option)
3N 380V/50Hz
(Special power supply for option)
Compressor Type Hermetic scroll type
Start mode Directly start(Soft start for option)
Quantity Unit 1 1 1 1 1 2 2 2 4 2 3 3 4
Water Side Heat exchanger Shell & coil(tube) heat exchanger
Water flow m3/h 2.1 3.3 2.1 3.3 4.3 6.0 8.6 11.2 12.9 14.6 18.1 21.5 28.4
Water pressure drop kPa ≤45 ≤53 ≤45 ≤53 ≤55 ≤60 ≤60 ≤60 ≤65 ≤68 ≤70 ≤70 ≤75
Connection size DN DN25 DN25 DN25 DN25 DN25 DN32 DN32 DN50 DN50 DN50 DN50 DN65 DN80
Air Side Exchanger Finned tube heat exchanger
Rated Air flow m3/h 3500 6320 3500 6320 7500 12500 14800 14800 26000 26000 39000 39000 52000
Rated output power of fan motor W 120 250 120 250 370 550 750 750 1100 1100 1500 1500 2200
Protections 1. High pressure and low pressure protection, 
2. Anti-freezing protection, 
3. High temperature protection, 
4. Too big of the water temperature difference for outlet and inlet protection, 
5. Overload protection, 
6. Lack phase protection, 
7. Reverse phase protection, etc..
Refrigerant Throttle type Electronic expansion valve
Type R410a
Quantity kg 1.9 2.8 1.9 2.8 4.1 2.8×2 4.1×2 5.2×2 3.2×4 7.6×2 6.2×3 7.6×3 7.6×4
Noise DB(A) ≤55 ≤63 ≤55 ≤63 ≤65 ≤65 ≤66 ≤68 ≤70 ≤72 ≤73 ≤75 ≤78
Dimension mm 710x710x1100 990x990x1800 1000x2050x1850 2000x2050x1850
Wooden case package dimensions(LxWxH) mm 766x766x1146 1046x1046x1968 1056x2106x2018 2056x2106x2018
Net weight kg 108 135 108 135 165 340 400 485 605 660 835 840 1230
Gross weight kg 123 150 123 150 180 370 430 515 640 695 870 875 1265
Testing conditions:
1. Application side initial water temperature: 15ºC, end temperature 55ºC, max. temperature 60ºC.
2. Ambient temperature dry bulb 20ºC, wet bulb 15ºC.
The above parameters are based on Refrigearnt R410a, for parameters based on other refrigerant please contact us.
The above parameters may have some differences from the final product because of products updating, so above information is not the provision of any business contract. Please refer to final product label, or refer to us for any information. Our company keeps the right to interpret.

Welcome to MES!